DP port: connects to the display module.
Appearance
DP Port
Connects to the display module for communication and
power supply.
Button
Appearance
SW Button
When the smart cooling product is shut down and the
admin user has logged in, if you hold down the button for
more than 10s, a red frame is added to the button that
involves a risky operation on the display module within 5
minutes. You can press and hold down the button for 10s
to enter the risky operation screen. Exercise caution
because a risky operation may affect system data.
2.5 Working Modes
The unit runs in one of the following modes based on the real-time working
conditions and load.
Table 2-2 Working modes
Working Mode
Fan
Status
Water
Pump
Status
Compressor
Status
Dry mode (fan)
On
Off
Off
Wet mode (fan + spraying)
On
On
Off
Hybrid mode (dry mode +
auxiliary cooling mode)
On
Off
On
Hybrid mode (wet mode +
auxiliary cooling mode)
On
On
On
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
2 Product Description
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
25