6
Verifying the Installation
Table 6-1 System checklist
Check
Item
Expected Result
Check Result
Unit
The unit is installed properly without any tilt.
□ Passed □ Failed
Sundries (such as desiccant, cable ties, cable
ends, dust, iron scraps, copper wires, and
aluminum scraps) inside the cabinet have been
removed.
□ Passed □ Failed
Fan
The fan is secured.
□ Passed □ Failed
There are no sundries inside the fan.
□ Passed □ Failed
The fan blades rotate properly.
□ Passed □ Failed
Water
system
The water pump is secured.
□ Passed □ Failed
The water filter is secured.
□ Passed □ Failed
The liquid level sensor runs smoothly.
□ Passed □ Failed
Pipes are connected securely without leakage.
□ Passed □ Failed
The water tank is free of sundries inside and its
filter is unblocked.
□ Passed □ Failed
The drip pan is free of foreign matter inside
and its drainage port is unblocked.
□ Passed □ Failed
Compres
sor
The sheet metal fasteners on the compressor
have been removed.
□ Passed □ Failed
The bolts for securing the compressor are
tightened.
□ Passed □ Failed
Differen
tial
The pressure inlet tube is secured using cable
ties and not deformed.
□ Passed □ Failed
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
6 Verifying the Installation
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
98