Tab
Parameter
Description
System
Optional
Parts
Return air sensor
Enables or disables a sensor.
Supply air sensor
Enables or disables a sensor.
Cold aisle sensor
Enables or disables a sensor.
Hot aisle sensor
Enables or disables a sensor.
Outdoor intake air
sensor 3
Enables or disables a sensor.
Cold aisle
temperature and
humidity sharing
This function can be enabled only
when at least one smart cooling
product in the teamwork group is
equipped with cold aisle T/H sensors. If
this function is enabled, the master
unit in the teamwork group collects
the cold aisle temperature and
humidity values from all units
equipped with cold aisle sensors, and
synchronizes the temperature and
humidity control type and setpoints to
all slave units.
Hot aisle temperature
and humidity sharing
This function can be enabled only
when at least one smart cooling
product in the group is equipped with
hot aisle T/H sensors. If this function is
enabled, the master unit in the
teamwork group collects the hot aisle
temperature and humidity values from
all units equipped with hot aisle
sensors, and synchronizes the
temperature and humidity control type
and setpoints to all slave units.
Supply air damper
● Disable: The air damper function of
the unit is disabled.
● AO Ctrl: Select AO Ctrl for AO-type
air dampers.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
7 Power-On Commissioning
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
104