3
Product Specifications
3.1 Technical Specifications
3.1.1 System Specifications (Building Scenario)
Table 3-1 System specifications
Item
Building Scenario
Maximum power
78.5 kW (default power)
Maximum
current
140 A (default current)
Total cooling
capacity
240 kW
1
Sensible cooling
capacity
240 kW
1
Sensible heat
ratio
100%
System
dimensions (H x
W x D)
3600 mm x 2438 mm x 4700 mm
Installation
scenario
Indoor
Power system
380–415 V AC, 3-phase, 50 Hz/60 Hz
Air filter level on
the indoor air
return side (EN
779)
G4
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
3 Product Specifications
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.