Start-up, ID run and use 19
Note:
If you change the motor parameters after the ID run, you need to repeat
the run.
Note:
If you have already parameterized your application using scalar motor
control mode and you need to change to vector:
•
Set parameter
Motor control mode
selection to
Vector
.
•
for I/O controlled drive, check parameters in groups
,
•
for torque controlled drive, check also parameters in group
.
ID run steps
Warning!
Make sure it is safe to run the procedure.
1.
Open the
Main
menu.
2.
Select the
Parameters
submenu.
3.
Select
All parameters
.
4.
Select
and press OK.
5.
Select
, select the wanted ID mode and press OK.
warning message is shown before you press
Start.
The panel LED starts to blink green to indicate an active warning.
6.
Press Start to start the ID run.
Do not to press any control panel keys during the ID run. If you need to stop
the ID run, press Stop.
After the ID run is completed, the status light stops blinking.
If the ID run fails, the panel shows the fault