Fault tracing 345
64B2
User set fault
Loading of user parameter
set failed because
• requested set does not
exist
• set is not compatible with
control program
• drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1
Kernel overload
Operating system error.
Reboot the control unit (using
parameter
)
or by cycling power. If the problem
persists, contact your local ABB
representative
6581
Parameter system
Parameter load or save
failed.
Try forcing a save using parameter
. Retry.
6681
EFB comm loss
Programmable fault:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus
master (online/offline/error etc.).
Check cable connections to the
EIA-485 terminals 25, 26, 27 and 28 on
the control unit.
6682
EFB config file
Embedded fieldbus (EFB)
configuration file could not
be read.
Contact your local ABB representative.
6683
EFB invalid
parameterization
Embedded fieldbus (EFB)
parameter settings
inconsistent or not
compatible with selected
protocol.
Check the settings in parameter group
.
6684
EFB load fault
Embedded fieldbus (EFB)
protocol firmware could not
be loaded.
Contact your local ABB representative.
Version mismatch between
EFB protocol firmware and
drive firmware.
6685
EFB fault 2
Fault reserved for the EFB
protocol application.
Check the documentation of the
protocol.
6686
EFB fault 3
Fault reserved for the EFB
protocol application.
Check the documentation of the
protocol.
6882
Text 32-bit table
overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
6885
Text file overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
7081
Control panel loss
Programmable fault:
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
7082
I/O module comm
loss
Communication between IO
module and drive is not
working properly.
Replace the drive.
Code
(hex) Fault / Aux. code
Cause
What to do
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...