350 Fault tracing
000D (Permanent magnet motors
only)
Second acceleration did not
finish within reasonable
time.
Contact your local ABB representative.
000E…0010 Internal error.
Contact your local ABB representative.
0011 (Synchronous reluctance
motors only)
Pulse test error.
Contact your local ABB representative.
0013 (Asynchronous motors only)
Motor data error.
Check that the motor nominal value
settings in the drive are the same as in
the motor nameplate.
Contact your local ABB representative.
FF8E
EFB force trip
A fault trip command has
been received through the
embedded fieldbus
interface.
Check the fault information provided
by the PLC.
Code
(hex) Fault / Aux. code
Cause
What to do