212 Parameters
KTY83 analog I/O
KTY83 sensor connected to the analog input selected
by parameter
and an
analog output.
The following settings are required:
• Set the hardware jumper or switch related to the
analog input to
U
(voltage). Any change must be
validated by a control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
V
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
The analog output feeds a constant current through
the sensor. As the resistance of the sensor increases
along with its temperature, the voltage over the
sensor increases. The voltage is read by the analog
input and converted into degrees.
12
1 × Pt1000 analog I/O
Pt1000 sensor connected to a standard analog input
selected by parameter
and an analog output.
The following settings are required:
• Set the hardware jumper or switch related to the
analog input to
U
(voltage). Any change must be
validated by a control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
V
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
The analog output feeds a constant current through
the sensor. As the resistance of the sensor increases
along with its temperature, the voltage over the
sensor increases. The voltage is read by the analog
input and converted into degrees.
13
2 × Pt1000 analog I/O
As selection
, but with two
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
14
3 × Pt1000 analog I/O
As selection
, but with three
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
15
Ni1000
Ni1000 sensor connected to the analog input selected
by parameter
and an
analog output.
The following settings are required:
• Set the hardware jumper or switch related to the
analog input to
U
(voltage). Any change must be
validated by a control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
V
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
The analog output feeds a constant current through
the sensor. As the resistance of the sensor increases
along with its temperature, the voltage over the
sensor increases. The voltage is read by the analog
input and converted into degrees.
16
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...