Fault tracing 337
A8C0 ULC invalid speed
table
User load curve: X-axis
points (speed) are not valid.
Check that points fulfill conditions.
See parameter
A8C1
ULC overload
warning
User load curve: Signal has
been too long over the
overload curve.
See parameter
A8C4 ULC underload
warning
User load curve: Signal has
been too long under the
underload curve.
See parameter
A8C5 ULC invalid
underload table
User load curve: Underload
curve points are not valid.
Check that points fulfill conditions.
See parameter
A8C6 ULC invalid overload
table
User load curve: Overload
curve points are not valid.
Check that points fulfill conditions.
See parameter
A8C8 ULC invalid
frequency table
User load curve: X-axis
points (frequency) are not
valid.
Check that points fulfill conditions. -
500.0 Hz <
<
< 500.0 Hz. See
parameter
A981
External warning 1
(Editable message
text)
Programmable
warning:
Fault in external device 1.
Check the external device.
Check setting of parameter
A982
External warning 2
(Editable message
text)
Programmable
warning:
Fault in external device 2.
Check the external device.
Check setting of parameter
A983
External warning 3
(Editable message
text)
Programmable
warning:
Fault in external device 3.
Check the external device.
Check setting of parameter
Code
(hex) Warning / Aux. code
Cause
What to do
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...