Parameters 253
Data storage parameter 19.
0
-32768…32767
16-bit data.
1 = 1
Data storage parameter 20.
0
-32768…32767
16-bit data.
1 = 1
49
Communication settings for the control panel port on
the drive.
Defines the node ID of the drive. All devices connected
to the network must have a unique node ID.
Note:
For networked drives, it is advisable to reserve
ID 1 for spare/replacement drives.
Note:
Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
.
1
1…32
Node ID.
1 = 1
Defines the transfer rate of the link.
Note:
Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
.
38.4 kbps
38.4 kbit/s.
1
57.6 kbps
57.6 kbit/s.
2
86.4 kbps
86.4 kbit/s.
3
115.2 kbps
115.2 kbit/s.
4
230.4 kbps
230.4 kbit/s.
5
Sets a timeout for control panel (or PC tool)
communication. If a communication break lasts
longer than the timeout, the action specified by
parameter
is taken.
Note:
Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
.
10.0 s
0.3…3000.0 s
Panel/PC tool communication timeout.
10 = 1 s
Selects how the drive reacts to a control panel (or PC
tool) communication break.
Note:
Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
.
No action
No action taken.
0
Fault
Drive trips on
1
Last speed
Drive generates an
warning and
freezes the speed to the level the drive was operating
at. The speed is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...