380
Fieldbus control through the embedded fieldbus interface (EFB)
The new settings will take effect when the drive is powered up the next time, or
when they are validated by parameter
).
Setting the drive control parameters
After the embedded fieldbus interface has been set up, check and adjust the
drive control parameters listed in the table below. The
Setting for fieldbus
control
column gives the value or values to use when the embedded fieldbus
signal is the desired source or destination for that particular drive control
signal. The
Function/Information
column gives a description of the parameter.
…
…
With the default
settings, TPDO1
contains 16-bit
status word and
two 16-bit actual
values and
RPDO1 contains
16-bit control word
and two 16-bit
reference values.
Defines the objects mapped to
PDOs to and from the drive.
Validates the settings of the
configuration parameters.
Parameter
Setting for
fieldbus control
Function/Information
CONTROL COMMAND SOURCE SELECTION
Selects fieldbus as the source for the start
and stop commands when EXT1 is selected
as the active control location.
Selects fieldbus as the source for the start
and stop commands when EXT2 is
selected as the active control location.
SPEED REFERENCE SELECTION
EFB ref1
Selects a reference received through the
embedded fieldbus interface as speed
reference 1.
EFB ref1
Selects a reference received through the
embedded fieldbus interface as speed
reference 2.
TORQUE REFERENCE SELECTION
EFB ref1
Selects a reference received through the
embedded fieldbus interface as torque
reference 1.
Parameter
Setting for
fieldbus control
Function/Information
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...