Fieldbus control through the embedded fieldbus interface (EFB)
357
the EFB CW as the source of drive control commands (such as start/stop,
emergency stop, selection between external control locations 1/2, or fault
reset). The drive switches between its states according to the bit-coded
instructions of the CW.
The fieldbus CW is either written to the drive as it is or the data is converted.
See section
on page
The fieldbus Status Word (SW) is a 16-bit or 32-bit packed boolean word. It
contains status information from the drive to the fieldbus controller. The drive
SW is either written to the fieldbus SW as it is or the data is converted. See
section
References
EFB references 1 and 2 are 16-bit or 32-bit signed integers. The contents of each
reference word can be used as the source of virtually any signal, such as the
speed, frequency, torque or process reference. In embedded fieldbus
communication, references 1 and 2 are displayed by
respectively. Whether the references are scaled or not
depends on the settings of
and
. See section
Actual values
Fieldbus actual signals (ACT1 and ACT2) are 16-bit or 32-bit signed integers.
They convey selected drive parameter values from the drive to the master.
Whether the actual values are scaled or not depends on the settings of
. See section
on page
Data input/outputs
Data input/outputs are 16-bit or 32-bit words containing selected drive
parameter values. Parameters
define the
addresses from which the master either reads data (input) or to which it writes
data (output).
Register addressing
The address field of Modbus requests for accessing holding registers is 16 bits.
This allows the Modbus protocol to support addressing of 65536 holding
registers.
Historically, Modbus master devices used 5-digit decimal addresses from 40001
to 49999 to represent holding register addresses. The 5-digit decimal
addressing limited to 9999 the number of holding registers that could be
addressed.
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...