Program features 65
Frequency trim connection
Frequency trim is added at 28.02 Frequency ref ramp out and the final frequency
reference is generated after the trim addition. At the moment, no parameter is
available to see the final frequency reference after adding frequency trim.
Note
: PID trim output auto connection is disabled in the firmware when the
drive is stopped with the
value
. In other words, PID trim output actual (
) will not be added to the respective speed, torque
and frequency reference chains during ramp stop or emergency stop.
Mechanical brake control
A mechanical brake can be used for holding the motor and driven machinery at
zero speed when the drive is stopped, or not powered. The brake control logic
observes the settings of parameter group
as well
as several external signals, and moves between the states presented in the
diagram on page
. The tables below the state diagram detail the states and
transitions. The timing diagram on page
shows an example of a close-open-
close sequence.
Inputs of the brake control logic
The start command of the drive (bit 5 of
) is the main
control source of the brake control logic.
Outputs of the brake control logic
The mechanical brake is controlled by bit 0 of parameter
. This bit should be selected as the source of a relay output (or a digital
output) which is then wired to the brake actuator through a relay. See the wiring
example on page
.
The brake control logic, in various states, will request the drive control logic to
hold the motor, or ramp down the speed. These requests are visible in
parameter
.
28.02 Frequency ref ramp out
Frequency trim
Final frequency
+
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...