116 Parameters
Specifies the analog input limits to be supervised. See
0000h
0000h…FFFFh
Activation of analog input supervision.
1 = 1
Activates/deactivates analog input supervision for
each control location (see section
on page
).
When a control location does not utilize AI for
referencing, you can use this parameter to deactivate
AI supervision (
). This hides the AI supervision
function (
) for the selected control location.
0b0000
0000h…FFFFh
Activation of analog input supervision.
1 = 1
Displays the value of analog input AI1 in mA or V
(depending on whether the input is set to current or
voltage by a hardware setting).
This parameter is read-only.
-
0.000...22.000 mA or
0.000...11.000 V
Value of analog input AI1.
1000 = 1 unit
Displays the value of analog input AI1 after scaling.
See parameters
and
.
This parameter is read-only.
-
-32768 … 32767
Scaled value of analog input AI1.
1 = 1
Defines the forced value that can be used instead of
the true reading of the input. See parameter
.
-
-
1000 = 1 -
Selects the unit for readings and settings related to
analog input AI1.
V
Volts.
2
mA
Milliamperes.
10
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Description
0
AI1 < MIN
1 = Minimum limit supervision of AI1 active.
1
AI1 > MAX
1 = Maximum limit supervision of AI1 active.
2
AI2 < MIN
1 = Minimum limit supervision of AI2 active.
3
AI2 > MAX
1 = Maximum limit supervision of AI2 active.
4…15
Reserved
Bit
Name
Description
0
AI1 Ext1
1 = AI1 supervision is active when EXT1 is used.
1
AI1 Ext2
1 = AI1 supervision is active when EXT2 is used.
2
AI1 Local
1 = AI1 supervision is active when local control is used.
3
Reserved
4
AI2 Ext1
1 = AI2 supervision is active when EXT1 is used.
5
AI2 Ext2
1 = AI2 supervision is active when EXT2 is used.
6
AI2 Local
1 = AI2 supervision is active when local control is used.
7…15
Reserved
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...