
192 Parameters
Selects which indications are given when one or both
Safe torque off (STO) signals are switched off or lost.
The indications also depend on whether the drive is
running or stopped when this occurs.
The tables at each selection below show the
indications generated with that particular setting.
Notes:
• This parameter does not affect the operation of
the STO function itself. The STO function will
operate regardless of the setting of this
parameter: a running drive will stop upon removal
of one or both STO signals, and will not start until
both STO signals are restored and all faults reset.
• The loss of only one STO signal always generates a
fault as it is interpreted as a malfunction.
For more information on the STO, see chapter
The
Safe torque off function
in the hardware manual of
the drive.
Fault/Fault
0
Fault/Warning
1
Fault/Event
2
No.
Name/Value
Description
Default
FbEq 16
Inputs
Indication (running or stopped)
IN1
IN2
0
0
0
1
Fault
1
0
1
1
(Normal operation)
Inputs
Indication
IN1
IN2
Running
Stopped
0
0
Warning
0
1
Fault
1
0
Fault
1
1
(Normal operation)
Inputs
Indication
IN1 IN2
Running
Stopped
0
0
0
1
1
0
Fault
Fault
1
1
(Normal operation)
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...