Fieldbus control through the embedded fieldbus interface (EFB)
411
6061h 0
Mode of
Operation
Display
INT8
RO
This object provides the actual
operation mode.
The following value definition is valid:
0 = no mode change / no mode
assigned
1 = profile position mode (not
supported)
2 = velocity mode
3 = profile velocity mode
4 = profile torque mode
5 = reserved
6 = homing mode (not supported)
7 = interpolated position mode (not
supported)
8 = cyclic synchronous position mode
(not supported)
9 = cyclic synchronous velocity mode
10 = cyclic synchronous torque mode
6069h 0
Velocity
sensor actual
value
INT32 RO
This object provides the value read
from a velocity sensor.
606Bh 0
Velocity
demand value
INT32 RO
This object provides the output value of
the trajectory generator.
606C
h
0
Velocity
actual value
INT32 RO
This object provides the actual velocity
value derived either from the velocity
sensor or the position sensor.
6071h 0
Target torque INT16 RWW
This object indicates the input value for
the torque controller in profile torque
mode.
6072h 0
Max torque
U6
RWW
This object indicates the maximum
permissible torque in the motor. 10 =
1%
6073h 0
Max current
U6
RWW
This object indicates the maximum
permissible torque creating current in
the motor. 10 = 1%
6077h 0
Torque actual
value
INT16 RO
This object provides the actual value of
the torque. It shall correspond to the
instantaneous torque in the motor. 10 =
1%
6083h 0
Profile
acceleration
U32
RWW
This object defines the commanded
acceleration.
This object is used in the profile
velocity mode.
Index
Sub-
inde
x
Name
Type
Access Description
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...