330 Fault tracing
Warning messages
Note:
The list also contains events that only appear in the Event log.
Code
(hex) Warning / Aux. code
Cause
What to do
64FF
Fault reset
A fault has been reset from
the panel, Drive composer PC
tool, fieldbus or I/O.
Event. Informative only.
A2A1
Current calibration
Current offset and gain
measurement calibration will
occur at next start.
Informative warning. (See parameter
A2B1
Overcurrent
Output current has exceeded
internal fault limit.
In addition to an actual
overcurrent situation, this
warning may also be caused
by an earth fault or supply
phase loss.
Check motor load.
Check acceleration times in parameter
group
(speed control),
(torque control) or
(frequency control).
Also check parameters
and
.
Check motor and motor cable
(including phasing and delta/star
connection).
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable. See chapter
Electrical
installation
, section
Checking the
insulation of the assembly
in the
hardware manual of the drive.
Check there are no contactors opening
and closing in motor cable.
Check that the start-up data in
parameter group
corresponds to the motor rating plate.
Check that there are no power factor
correction capacitors or surge
absorbers in motor cable.
A2B3
Earth leakage
Drive has detected load
unbalance typically due to
earth fault in motor or motor
cable.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable. See chapter
Electrical
installation
, section
Checking the
insulation of the assembly
in the
hardware manual of the drive. If an
earth fault is found, fix or change the
motor cable and/or motor.
If no earth fault can be detected,
contact your local ABB representative.
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...