Parameters 291
Selects the type of the motor identification routine
(ID run) performed at the next start of the drive.
During the ID run, the drive will identify the
characteristics of the motor for optimum motor
control.
If no ID run has been performed yet (or if default
parameter values have been restored using
parameter
), this parameter
is automatically set to
, signifying that an ID
run must be performed.
After the ID run, the drive stops and this parameter is
.
Notes:
• To ensure that the ID run can work properly, the
drive limits in group
(maximum speed
and minimum speed, and maximum torque and
minimum torque) must to be large enough (the
range specified by the limits must be wide enough.
If eg. speed limits are less than the motor nominal
speed, the ID run cannot be completed.
• For the
ID run, the machinery must
always be de-coupled from the motor.
• With a permanent magnet or synchronous
reluctance motor, a
,
or
ID run requires that the motor shaft is NOT locked
and the load torque is less than 10%.
• Once the ID run is activated, it can be canceled by
stopping the drive.
• The ID run must be performed every time any of the
motor parameters (
…
) have been
changed.
• With scalar control mode (
), the ID run is not requested
automatically. However, an ID run can be
performed for more accurate torque estimation.
• Ensure that the Safe torque off and emergency
stop circuits (if any) are closed during the ID run.
• Mechanical brake (if present) is not opened by the
logic for the ID run.
• This parameter cannot be changed while the drive
is running.
None
No motor ID run is requested. This mode can be
selected only if the ID run
) has already
been performed once.
0
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280