Parameters 273
Restores the original settings of the control program,
ie. parameter default values.
Note:
This parameter cannot be changed while the
drive is running.
Done
Restoring is completed.
0
Restore defaults
All editable parameter values are restored to default
values, except
• motor data and ID run results
• end user texts, such as customized warnings and
faults (external faults and changed), and the drive
name
• control panel/PC communication settings
• fieldbus adapter settings
• parameter
differentiated defaults implemented by it.
• user lock configuration parameters
.
8
Clear all
All editable parameter values are restored to default
values, except
• end user texts, such as customized warnings and
faults (external faults and changed), and the drive
name
• control panel/PC communication settings
• fieldbus adapter settings (clears entire existing
settings)
• parameter
differentiated defaults implemented by it.
• user lock configuration parameters
.
PC tool communication is interrupted during the
restoring.
62
Reset all fieldbus
settings
Restores all fieldbus and communication related
settings to default values.
Note
: Fieldbus, control panel and PC tool
communication are interrupted during the restore.
32
Reset home view
Restores the Home view layout to show the values of
the default parameters.
512
Reset end user texts
Restores all end user texts to default values, including
the drive name, contact info, customized fault and
warning texts and currency unit.
If the value of parameter
is set to
User Text,
then the PID unit is also reset. If parameter
has
some other value, the PID unit cannot be reset.
1024
Reset motor data
Restores all motor nominal values and motor ID run
results to default values.
2
All to factory defaults
Restores settings and all editable parameters back to
initial factory values, except
the differentiated defaults implemented by
parameter 95.20.
34560
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...