Parameters 287
0.00000 … 10.00000
p.u
Quadrature axis inductance in per unit.
-
Defines the permanent magnet flux.
Note:
This parameter is valid only for permanent
magnet motors.
0.00000 p.u.
0.00000 … 2.00000 p.u Permanent magnet flux in per unit.
-
Defines the stator resistance
R
S
of the motor model.
0.00000
ohm
0.00000…
100.00000 ohm
Stator resistance.
-
Defines the rotor resistance
R
R
of the motor model.
Note:
This parameter is valid only for asynchronous
motors.
0.00000
ohm
0.00000…
100.00000 ohm
Rotor resistance.
-
Defines the main inductance
L
M
of the motor model.
Note:
This parameter is valid only for asynchronous
motors.
0.00 mH
0.00…100000.00 mH
Main inductance.
1 = 10000
mH
Defines the leakage inductance
L
S
.
Note:
This parameter is valid only for asynchronous
motors.
0.00 mH
0.00…100000.00 mH
Leakage inductance.
1 = 10000
mH
Defines the direct axis (synchronous) inductance.
Note:
This parameter is valid only for permanent
magnet motors.
0.00 mH
0.00 …100000.00 mH
Direct axis inductance.
1 = 10000
mH
Defines the quadrature axis (synchronous)
inductance.
Note:
This parameter is valid only for permanent
magnet motors.
0.00 mH
0.00 …100000.00 mH
Quadrature axis inductance.
1 = 10000
mH
99
Motor configuration settings.
Selects the motor type.
Note:
This parameter cannot be changed while the
drive is running.
Asynchronous motor
Standard squirrel cage AC induction motor
(asynchronous induction motor).
0
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...