232 Parameters
Used
Process PID controller output frozen.
1
DI1
Digital input DI1 (
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
Supervision 1
21
Supervision 2
Bit 1 of
22
Supervision 3
.
23
Source selection (see
).
-
Defines a deadband around the setpoint. Whenever
process feedback enters the deadband, a delay timer
starts. If the feedback remains within the deadband
longer than the delay (
),
the PID controller output is frozen. Normal operation
resumes after the feedback value leaves the
deadband.
0.00
0……200000.0
Deadband range.
1=1
Delay for the deadband. See parameter
0.0 s
0.0 … 3600.0 s
Delay for deadband area.
1 = 1 s
Defines the start limit for the sleep function. If the
value is 0.0, set 1 sleep mode is disabled.
The sleep function compares the motor speed to the
value of this parameter. If the motor speed remains
below this value longer than the sleep delay defined
by
, the drive enters the sleep
mode and stops the motor.
0.0
0.0…200000.0
Sleep start level.
1 = 1
No.
Name/Value
Description
Default
FbEq 16
Setpoint
Time
Feedback
PID controller
output
PID controller
output frozen