294 Parameters
Differences in the default values between 50 Hz and 60 Hz
supply frequency settings
Parameter
bit 0 changes the drive parameter default
values according to the supply frequency, 50 Hz or 60 Hz. The bit is set
according to the market before the drive is delivered.
If you need to change from 50 Hz to 60 Hz, or vice versa, change the value of the
bit and then do a complete reset to the drive (
). After
that you have to reselect the macro to be used.
The table below shows the parameters whose default values depend on the
supply frequency setting. The supply frequency setting, with the type
designation of the drive, also affects group
parameter values
(not listed in the table).
No.
Name
bit 0
Supply frequency 60 Hz
= 50 Hz
bit 0
Supply frequency 60 Hz
= 60 Hz
11.45
Freq in 1 at scaled max
1500.000
1800.000
1500.000
1800.000
1500.0
1800.0
300.00 rpm
360.00 rpm
600.00 rpm
720.00 rpm
900 .00 rpm
1080.00 rpm
1200.00 rpm
1440.00 rpm
22.30
1500.00 rpm
1800.00 rpm
2400.00 rpm
2880.00 rpm
3000.00 rpm
3600.00 rpm
5.00 Hz
6.00 Hz
10.00 Hz
12.00 Hz
15.00 Hz
18.00 Hz
20.00 Hz
24.00 Hz
25.00 Hz
30.00 Hz
40.00 Hz
48.00 Hz
50.00 Hz
60.00 Hz
-1500.00 rpm
-1800.00 rpm
1500.00 rpm
1800.00 rpm
-50.00 Hz
-60.00 Hz
50.00 Hz
60.00 Hz
150.00 rpm
180.00 rpm
15.00 Hz
18.00 Hz
500.00 rpm
500.00 rpm
1500.00 rpm
1800.00 rpm
50.00 Hz
60.00 Hz
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...