Fieldbus control through the embedded fieldbus interface (EFB)
353
(default)
Enables/disables communication loss
monitoring and defines the means for
resetting the counter of the
communication loss delay.
3.0 s (default)
Defines the timeout limit for the
communication monitoring.
0 ms (default)
Defines a response delay for the drive.
(default)
Selects the control profile used by the
drive. See section
(page
(default
),
,
,
(default for
,
Defines the types of fieldbus references 1
and 2. The scaling for each reference type
is defined by parameters
.
With the
setting, the
type is selected automatically according to
the currently active drive control mode.
(default
),
(default for
,
,
Defines the types of actual values 1 and 2.
The scaling for each actual value type is
defined by parameters
. With
the
setting, the type is
selected automatically according to the
currently active drive control mode.
Defines the source of actual values 1 and 2
when the
) is set to
.
(default)
Defines the mapping between parameters
and holding registers in the
400001…465536 (100…65535) Modbus
register range.
(default)
Defines the order of the data words in the
Modbus message frame.
Parameter
Setting for
fieldbus control
Function/Information