Parameters 259
Displays the raw (unmodified) status word for
debugging purposes.
This parameter is read-only.
-
0...FFFFFFFFh
Status word sent by the drive to the controller.
1 = 1
This parameter tells the CANopen NMT state of the
= [1] Modbus RTU, this
parameter is hidden.
Uninitialized
Uninitialized
Node is not initialized.
0
Stopped
Node is in STOPPED state.
4
Operational
Node is in OPERATIONAL state.
5
Pre-operational
Node is in PRE-OPERATIONAL state.
127
This parameter defines where communication
configuration for the device comes from.
Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
(
).
= [1] Modbus RTU, this
parameter is hidden.
CAN objects
Drive parameters
0
CAN objects
Communication configuration is written by CANopen
master to CANopen objects. The configuration can be
saved into the drive’s non-volatile memory. In that
case, the parameters don’t need to be set every time
the system is powered on
1
Defines the scaling value for Transparent 16
communication profile.
Changes to this parameter take effect after the
control unit is rebooted or the new settings
validated by parameter
).
= [1] Modbus RTU, this
parameter is hidden.
99
0...65535
Actual values and reference values are multiplied by
this value + 1 in the object dictionary.
1 = 1
Defines the communication profile used by the
protocol.
Changes to this parameter take effect after the
control unit is rebooted or the new settings validated
(
).
ABB Drives
ABB Drives control profile (with a 16-bit control word) 0
Transparent
Transparent control profile (with a 16 or 32-bit control
word).
Note: This selection is applicable only to Modbus.
2
DCU Profile
DCU control profile (with a 16 or 32-bit control word)
5
CiA 402
CiA 402 control profile.
Note: This selection is applicable only to CANopen.
7
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...