174 Parameters
Min (ref1, ref2)
The smaller of the reference sources is used as
frequency reference 1.
4
Max (ref1, ref2)
The greater of the reference sources is used as
frequency reference 1.
5
Determines how constant frequencies are selected,
and whether the rotation direction signal is
considered or not when applying a constant
frequency.
0b00001
0b0000...0b1111
Constant frequency configuration word.
1 = 1
When bit 0 of parameter
is 0 (Separate), selects a source that
activates constant frequency 1.
When bit 0 of parameter
is 1 (Packed), this parameter and parameters
select three sources whose states
activate constant frequencies as follows:
Always off
Always off
0 (always off).
0
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Information
0
Const freq
mode
1 = Packed: 7 constant frequencies are selectable using the three
sources defined by parameters
and
.
0 = Separate: Constant frequencies 1, 2 and 3 are separately
activated by the sources defined by parameters
respectively. In case of conflict, the constant frequency with
the smaller number takes priority.
1
Direction
enable
1 = Start dir: To determine running direction for a constant
frequency, the sign of the constant frequency setting (parameters
) is multiplied by the direction signal (forward: +1,
reverse: -1). This effectively allows the drive to have 14 (7 forward, 7
reverse) constant frequencies if all values in
…
are
positive.
WARNING!
If the direction signal is reverse and the active
constant frequency is negative, the drive will run in the
forward direction.
0 = According to Par: The running direction for the constant
frequency is determined by the sign of the constant speed setting
(parameters
).
2...15
Reserved
Source defined
by par.
Source defined
by par.
Source defined
by par.
Constant frequency
active
0
0
0
None
0
0
0
Constant frequency 1
0
0
0
Constant frequency 2
1
1
0
Constant frequency 3
0
0
1
Constant frequency 4
1
0
1
Constant frequency 5
0
1
1
Constant frequency 6
1
1
1
Constant frequency 7
Summary of Contents for ACS280