110 Parameters
Selects the relay outputs that will be controlled by
. The signals connected to the relay
outputs can be overridden for eg. testing purposes. A
is provided for
each relay output, and its value is applied whenever
the corresponding bit in this parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
).
0000h
0000h…FFFFh
Override selection for relay outputs.
1 = 1
Contains the values of relay outputs that are used
instead of the connected signals if selected in
. Bit 0 is the forced
value for RO1.
This provides the possibility to test the drive
functionality without the plant wiring. Ton and Toff
delays are passed.
0000h…FFFFh
Forced RO values.
1 = 1
Selects a drive signal to be connected to relay output
RO1.
Not energized
Output is not energized.
0
Energized
Output is energized.
1
Ready run
Bit 1 of
Enabled
4
Started
Bit 5 of
.
5
Magnetized
Bit 1 of
6
Running
Bit 6 of
.
7
Ready ref
8
At setpoint
Bit 8 of
.
9
Reverse
.
10
Zero speed
.
11
Above limit
Bit 10 of
12
Warning
13
Fault
14
Fault (-1)
Inverted bit 3 of
15
Fault/Warning
A warning or fault is active.
16
Overcurrent
A drive is tripped to overcurrent fault.
17
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
1 = Force RO1 to value of bit 0 of parameter
mode).
1…15
Reserved
Bit
Value
0
Forced value (0 or 1) for parameter
1…15
Reserved
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...