22 Default control connection
Default control connections
Terminal sizes: 0.5 mm² … 1 mm²
Notes:
1)
In scalar control (default): See parameter group
In vector control: See parameter group
Select the correct control mode from the
Motor data
view or with parameter
.
2)
Ground the outer shield of the cable 360 degrees under the grounding clamp
on the grounding shelf for the control cables.
3)
Select voltage or current for inputs AI1 and AI2 and output AO with
parameters
, respectively.
Terminals
Descriptions
Digital I/O connections
3
24 V
Aux. +24 V DC, max 200 mA
4
DGND
Aux. voltage output common
1
DI1
Stop (0) / Start (1)
2
DI2
Forward (0) / Reverse (1)
Analog I/O
5
AI1/A3
Speed reference (0…10V)
6
AI2/AI4
Not used
9
GND
Analog output circuit common
8
AO1/DO1
AO: Output frequency (0…10V)
7
10V
Ref. v10 V DC
CANopen protocal
10
CAN-H
Embedded CANopen (CAN)
11
CAN-L
12
GND
EIA-485 Modbus RTU
13
A-
Embedded Modbus RTU (EIA-485)
14
B+
15
GND
Relay output
16
RO NC
No fault [Fault (-1)]
17
RO COM
18
RO NO
Safe torque off (STO)
19
S+
Safe torque off function (STO).
Connected at factory.
Drive starts only when both circuits
are closed."
20 SGND
21
S1
22 S2
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...