Fault tracing 349
FF61
ID run
Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group
.
Check that no external control system
is connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits prevent
the completion of the ID run. Restore
parameters to default settings and try
again.
Check that the motor shaft is not
locked.
0001 Maximum current limit too
low.
Check settings of parameters
and
. Make sure that
>
Check that the drive is dimensioned
correctly according to the motor.
0002 Maximum speed limit or
calculated field weakening
point too low.
Check settings of parameters
•
•
•
•
•
Make sure that
•
> (0.55 ×
) >
(0.50 × synchronous speed)
•
< 0, and
• supply voltage > (0.66 ×
).
0003 Maximum torque limit too
low.
Check settings of parameter
, and the torque
limits in group
.
Make sure that the maximum torque
limit in force is greater than 100%.
0004 Current measurement
calibration did not finish
within reasonable time
Contact your local ABB representative.
0005…0008 Internal error.
Contact your local ABB representative.
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
Contact your local ABB representative.
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
Contact your local ABB representative.
000B (Asynchronous motors only)
Speed dropped to zero
during ID run.
Contact your local ABB representative.
000C (Permanent magnet motors
only)
First acceleration did not
finish within reasonable
time.
Contact your local ABB representative.
Code
(hex) Fault / Aux. code
Cause
What to do
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...