18 Start-up, ID run and use
Scalar mode is not recommended for permanent magnet motors.
5.
Set the nominal motor values:
•
Nominal power
•
Nominal current
•
Nominal voltage
•
Nominal frequency
•
Nominal speed
•
Nominal torque (optional)
•
Nominal cosphi (optional)
6.
Examine the direction of the motor.
If it is necessary, set the motor direction with the
Phase order
setting or
with the phase order of the motor cable.
7.
In the
Motor control
view
,
set the start and stop mode.
8.
Set the acceleration time and the deceleration time.
Note:
The speed acceleration and deceleration ramp times are based on
the value in parameter
9.
Set the maximum and minimum speed or frequency. For more information,
see parameters
.
10.
Tune the drive parameters to the application. You can use the Assistant
control
panel (ACS-AP-x), or the Drive Composer PC tool with the drive.
Do the identification (ID) run
Background information
The drive automatically estimates motor characteristics using Standstill ID run
when the drive is started for the first time, and after any motor parameter
(group
) is changed. This is valid when:
•
parameter
selection is
and
•
parameter
selection is
.
In most applications there is no need to perform a separate ID run. Select the ID
run for demanding motor control connections. For example:
•
permanent magnet motor (PMSM) is used
•
drive operates near zero speed references, or
•
operation at torque range above the motor nominal torque, over a wide
speed range is needed.
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...