244 Parameters
Specifies a delay between a close command (that is,
when the brake control output is de-energized) and
when the drive stops modulating. This is to keep the
motor live and under control until the brake actually
closes.
Set this parameter equal to the value specified by the
brake manufacturer as the mechanical make-up time
of the brake.
0.00 s
0.00…60.00 s
Brake close delay.
100 = 1 s
Defines the brake close speed as an absolute value.
After motor speed has decelerated to this level, a
close command is given.
10.00 rpm
0.00…1000.00 rpm
Brake close speed.
See par.
45
Settings for the energy saving calculators.
See also section
(page
Energy saved in GWh compared to direct-on-line
motor connection. This parameter is incremented
when
rolls over.
This parameter is read-only (see parameter
).
-
0…65535 GWh
Energy savings in GWh.
1 = 1 GWh
Energy saved in MWh compared to direct-on-line
motor connection. This parameter is incremented
when
rolls over.
When this parameter rolls over, parameter
is incremented.
This parameter is read-only (see parameter
).
-
0…999 MWh
Energy savings in MWh.
1 = 1 MWh
Energy saved in kWh compared to direct-on-line
motor connection.
If the internal brake chopper of the drive is enabled,
all energy fed by the motor to the drive is assumed to
be converted into heat, but the calculation still
records savings made by controlling the speed. If the
chopper is disabled, then regenerated energy from
the motor is also recorded here.
When this parameter rolls over, parameter
is incremented.
This parameter is read-only (see parameter
).
-
0.0…999.9 kWh
Energy savings in kWh.
10 = 1 kWh
Energy saved in kWh compared to direct-on-line
motor connection.
This parameter is read-only (see parameter
).
-
0.0…214748364.7 kWh
Energy savings in kWh.
1 = 1 kWh
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...