338 Fault tracing
A984 External warning 4
(Editable message
text)
Programmable
warning:
Fault in external device 5.
Check the external device.
Check setting of parameter
A985 External warning 5
(Editable message
text)
Programmable
warning:
Fault in external device 5.
Check the external device.
Check setting of parameter
.
AF8C Process PID sleep
mode
The drive is entering sleep
mode.
Informative warning. See section
Sleep and boost functions for process
, and parameters
…
.
AF90 Autotune
The autotune routine has
been interrupted.
The code contains an auxiliary value
that specifies the reason for the
abortion. For details, see section
.
AFAA Autoreset
A fault is about to be
autoreset.
Informative warning. See the settings
in parameter group
.
AFE1
Emergency stop
(off2)
Drive has received an
emergency stop (mode
selection off2) command.
Check that it is safe to continue
operation. Then return emergency
stop push button to normal position.
Restart drive.
If the emergency stop was
unintentional, check the source
AFE2
Emergency stop (off1
or off3)
Drive has received an
emergency stop (mode
selection off1 or off3)
command.
AFEA Enable start signal
missing
(Editable message
text)
No enable start signal
received.
Check the setting of (and the source
selected by) parameter
.
AFE9 Start delay
The start delay is active and
the drive will start the motor
after a predefined delay.
Informative warning. See parameter
.
AFEB Run enable missing
No run enable signal is
received.
. Switch signal on (e.g.
in the fieldbus Control Word) or check
wiring of selected source.
AFED Enable to rotate
Signal enable to rotate has
not been received within a
fixed time delay of 240s.
Switch enable to rotate signal on (eg.
in digital inputs).
Check the setting of (and source
selected by) parameter
AFF6 Identification run
Motor ID run will occur at
next start.
Informative warning.
Code
(hex) Warning / Aux. code
Cause
What to do
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...