266 Parameters
0...65535
Defines the time-out time for the PDO.
0 = no timeout
other = if this PDO is enabled and not received for
event timer milliseconds,
is performed.
Note
: The timeout supervision is activated upon a
successful reception of the RPDO.
1=1 ms
Set the COB-ID of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after
the control unit is rebooted or the new settings
validated by parameter
Note
: If parameter
= [1] Modbus RTU, this
parameter is hidden.
0x0000
0x0000...0x07ff
COB-ID.
0 = RPDO disabled,
1 = use COB-ID from CiA 301 pre-defined connection
set, <other value> = use selected COB-ID.
1=1
Set the transmission type of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after
the control unit is rebooted or the new settings
validated by parameter
Note
: If parameter
= [1] Modbus RTU, this
parameter is hidden.
255
0...255
Transmission type.
0 = acyclic synchronous
1...240 = cyclic synchronous
252 = synchronous RTR only
253 = asynchronous RTR only
254…255 = asynchronous
1=1
Set the event timer of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after
the control unit is rebooted or the new settings
validated by parameter
Note
: If parameter
= [1] Modbus RTU, this
parameter is hidden.
0
0...65535
Event timer
0 = no timeout
other = if this PDO is enabled and has not been
transmitted for event timer milliseconds, a
transmission is forced
1=1 ms
Set the COB-ID of the PDO.
Changing this parameter has an effect only if
58.23
Configuration location
is
Drive parameters
and after
the control unit is rebooted or the new settings
validated by parameter
Note
: If parameter
= [1] Modbus RTU, this
parameter is hidden.
0x0000
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...