282 Parameters
This parameter can be used to improve the control
dynamics of a synchronous reluctance motor or a
salient permanent magnet synchronous motor.
As a rule of thumb, define a level to which the output
torque must rise with minimum delay. This will
increase the motor current and improve the torque
response at low speeds.
0.0%
0.0...1600.0%
Optimizer torque limit.
10 = 1%
Rotor time constant tuning.
This parameter can be used to improve torque
accuracy in closed-loop control of an induction motor.
Normally, the motor identification run provides
sufficient torque accuracy, but manual fine-tuning
can be applied in exceptionally demanding
applications to achieve optimal performance.
Note:
This is an expert level parameter and should not
be adjusted without appropriate skill.
100%
25…400%
Rotor time constant tuning.
1 = 1%
No.
Name/Value
Description
Default
FbEq 16