
Program features 39
Example
A fan has vibrations in the range of 540 to 690 rpm and 1180 to 1560 rpm. To
make the drive avoid these speed ranges,
• enable the critical speeds function by turning on bit 0 of parameter
,
and
• set the critical speed ranges as in the figure below.
Settings and diagnostics
• Critical speeds - Parameters
…
.
• Critical frequencies - Parameters
• Function input (speed) - Parameter
• Function output (speed) - Parameter
.
• Function input (frequency) - Parameter
• Function output (frequency) - Parameter
Events: -
Speed controller autotune
The speed controller of the drive can be automatically adjusted using the
autotune function. Autotuning is based on an estimation of the mechanical
time constant (inertia) of the motor and machine.
The autotune routine will run the motor through a series of
acceleration/deceleration cycles, the number of which can be adjusted by
parameter
. Higher values will produce more accurate results, especially if
the difference between initial and maximum speeds is small.
The maximum torque reference used during autotuning will be the initial torque
(that is, torque when the routine is activated) plus
, unless limited by the
maximum torque limit (parameter group
) or the nominal motor
540
690
1180
1560
1
Par.
= 540 rpm
2
Par.
= 690 rpm
3
Par.
= 1180 rpm
4
Par.
= 1560 rpm
1
2 3 4
(output of function)
(input of function)
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...