Parameters 249
Defines the maximum frequency value used to define
the acceleration ramp rate and the initial frequency
value used to define deceleration ramp rate (see
parameter group
). The
frequency acceleration and deceleration ramp times
are therefore related to this value (
not
to parameter
.
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds
to
20000 in eg. fieldbus communication.
50.00 Hz
0.10…1000.00 Hz
Acceleration/deceleration terminal/initial frequency.
10 = 1 Hz
Defines the 16-bit scaling of torque parameters. The
value of this parameter (in percent of nominal motor
torque) corresponds to 10000 in eg. fieldbus
communication.
100.0%
0.1…1000.0%
Torque corresponding to 10000 on fieldbus.
10 = 1%
Defines the 16-bit scaling of power parameters. The
value of this parameter corresponds to 10000 in the
fieldbus communication. The unit is selected by
parameter
(For 32-bit scaling see
1000.00
0.10…30000.00
Power corresponding to 10000 on fieldbus.
1 = 1 unit
Defines the 16-bit scaling of current parameters. The
value of this parameter corresponds to 10000 in
fieldbus, master/follower, etc. communication.
(For 32-bit scaling see
)
10000 A
0…30000 A
Current corresponding to 10000 on fieldbus.
1 = 1 A
Defines a speed corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface EFB). For example, with a
setting of 500, the fieldbus reference range of
0…20000 would correspond to a speed of
500…[
] rpm.
Note:
This parameter is effective only with the ABB
Drives communication profile.
0.00 rpm
0.00 … 30000.00 rpm
Speed corresponding to minimum fieldbus reference. 1 = 1 rpm
Defines a frequency corresponding to a zero
reference received from fieldbus (either the
embedded fieldbus interface, or interface EFB). For
example, with a setting of 30, the fieldbus reference
range of 0…20000 would correspond to a speed of
30…[
] Hz.
Note:
This parameter is effective only with the ABB
Drives communication profile.
0.00 Hz
0.00 … 1000.00 Hz
Speed corresponding to minimum fieldbus reference. 10 = 1 Hz
Defines a filter time for signals
500 ms
2…20000 ms
Motor speed signal filter time.
1 = 1 ms
Defines a filter time for signal
500 ms
2…20000 ms
Output frequency signal filter time.
1 = 1 ms
No.
Name/Value
Description
Default
FbEq 16
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...