70 Program features
Implementing the undervoltage control (power loss ride-through)
Implement the undervoltage control function as follows:
• Check that the undervoltage control function of the drive is enabled with
parameter
.
• Parameter
must be set to
(in vector mode) or
parameter
(in scalar mode) to make
flying start (starting into a rotating motor) possible.
If the installation is equipped with a main contactor, prevent its tripping at the
input power break. For example, use a time delay relay (hold) in the contactor
control circuit.
WARNING!
Make sure that the flying restart of the motor will not cause
any danger. If you are in doubt, do not implement the undervoltage
control function.
Voltage control and trip limits
The control and trip limits of the intermediate DC voltage regulator are relative
to the supply voltage as well as drive/inverter type. The DC voltage (
U
DC
) is
approximately 1.41 times the line-to-line supply voltage, and is displayed by
parameter
The following table shows the values of the selected DC voltage levels in volts.
Note that the absolute voltages vary according to drive/inverter type and AC
supply voltage range.
When adaptive voltage limit is enabled in parameter
:
DC voltage level [V]
95.01 Supply Voltage
See
AC supply voltage
range [V]
208…240
AC supply voltage
range [V]
380…415
AC supply
voltage range [V]
440…480
Automatic /
not used
Overvoltage fault limit
421
842
842
842
Overvoltage control limit
389
779
779
779
Internal brake chopper
start limit
389
760
760
760
Internal brake chopper
stop limit
379
745
745
745
Overvoltage warning limit
372
745
745
745
Undervoltage warning
limit
0.85×1.41× par
value
1)
0.85×1.41× par
value
1)
0.85×1.41×par
value
1)
0.85×1.41× par
value
1)
0.85×1.41×208
= 249
2)
0.85×1.41×380
= 455
2)
0.85×1.41×440
= 527
2)
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...