136 Parameters
Selects the enable signal warnings that will be
suppressed. This parameter can be used to prevent
these warnings from being added to the event log.
Whenever a bit of this parameter is set to 1, the
corresponding warning is suppressed.
0000h
0000h…FFFFh
Word for disabling enable signal warnings.
1 = 1
21
Start and stop modes; emergency stop mode and
signal source selection; DC magnetization settings.
Selects the motor start function for the vector motor
control mode, ie. when
set to
.
Notes
:
• The start function for the scalar motor control
• Starting into a rotating motor is not possible when
DC magnetizing is selected (
).
• With permanent magnet motors,
start
mode must be used.
• This parameter cannot be changed while the drive
is running.
See also section
on page
Fast
The drive pre-magnetizes the motor before start. The
pre-magnetizing time is determined automatically,
typically 200 ms to 2 s depending on motor size.
Select this mode if a high break-away torque is
required.
0
Const time
The drive pre-magnetizes the motor before start. The
pre-magnetizing time is defined by parameter
. This mode should be selected if
constant pre-magnetizing time is required (e.g. if the
motor start must be synchronized with the release of
a mechanical brake). This setting also guarantees the
highest possible break-away torque when the pre-
magnetizing time is set long enough.
WARNING!
The drive will start after the set
magnetizing time has passed even if motor
magnetization is not completed. In
applications where a full break-away torque is
essential, ensure that the constant magnetizing time
is long enough to allow generation of full
magnetization and torque.
1
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Description
0
Enable to rotate
1 = Warning
is suppressed.
1
Run enable missing 1 = Warning
is suppressed.
3…15
Reserved
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...