Fieldbus control through the embedded fieldbus interface (EFB)
379
RPDO1 COB-ID
RPDO6 COB-ID
RPDO21 COB-ID
1 (default) for
), 0 (default
for
Defines the COB-ID for the PDO
and also enables or disables it.
0= Disable this PDO
1= Enable this PDO with default
COB-ID
other= Enable this PDO with
given (COB-ID)
RPDO1 transmission type
RPDO6 transmission type
RPDO21 transmission type
255 (default)
Defines the transmission type of
the PDO.
0 = acyclic synchronous
1...240 = cyclic synchronous
254…255 = asynchronous
RPDO1 event timer
RPDO6 event timer
RPDO21 event timer
0 (default)
Defines the time-out time for the
PDO.
0 = no timeout
other = if this PDO is enabled and
not received for event timer
milliseconds, 58.14
Communication loss action is
performed
Note: The timeout supervision is
activated upon a successful
reception of the RPDO.
TPDO1 COB-ID
TPDO6 COB-ID
RPDO21 COB-ID
1 (default for
), 0 (default
for
Defines the COB-ID for the PDO
and also enables or disables it.
0 = Disable this PDO
1 = Enable this PDO with default
COB-ID
other = Enable this PDO with
given COB-ID
TPDO1 transmission type
TPDO6 transmission type
TPDO21 transmission type
255 (default)
Defines the transmission type of
the PDO.
0 = acyclic synchronous
1...240 = cyclic synchronous
252 = synchronous RTR only
253 = asynchronous RTR only
254…255 = asynchronous
TPDO1 event timer
TPDO6 event timer
TPDO21 event timer
100 (default for
0 (default for
)
Defines the time-out time for the
PDO.
0 = no timeout
other = if this PDO is enabled and
has not been transmitted for
event timer milliseconds, a
transmission is forced
Parameter
Setting for
fieldbus control
Function/Information
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...