120 Parameters
0.00… 100.00
AI2 value
100 = 1%
AI dead band value in percentage where 100% = 10 V
in voltage mode and 100% = 20 mA in current mode.
Applicable to both AI1 and AI2.
Note:
10% of AI dead band value is internally added in
firmware as AI dead band hysteresis positive and
negative.
(See section
on page
.)
0.40%
0%…100%
dead band value
1 = 1
13
Configuration of standard analog outputs.
Selects the analog outputs that will be forced to
values defined by parameters.
The true source signals of the analog outputs can be
overridden for eg. testing purposes. A forced value
parameter is provided for each analog output, and its
value is applied whenever the corresponding bit in
this parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
0000h
0000h…FFFFh
Forced values selector for analog output AO1.
1 = 1
Displays the value of AO1 in V.
This parameter is read-only.
-
0.000…11.000 V
Value of AO1.
1 = 1 V
Selects a signal to be connected to analog output
AO1.
Zero
None. 0
Motor speed used
1
Output frequency
3
Motor current
4
Motor current % of
motor nom
5
Motor torque
6
DC voltage
7
Output power
8
Speed ref ramp in
10
Speed ref ramp out
11
Speed ref used
12
Freq ref used
14
Process PID out
40.01 Process PID output actual
16
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
1 = Force AO1 to value of parameter
1…15
Reserved.
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...