340 Fault tracing
Fault messages
Code
(hex) Fault / Aux. code
Cause
What to do
1080
Backup/Restore
timeout
Panel or PC tool has failed to
communicate with the drive
when backup was being
made or restored.
Request backup or restore again.
1081
Rating ID fault
Drive software has not been
able to read the rating ID of
the drive.
Reset the fault to make the drive try to
reread the rating ID.
If the fault reappears, cycle the power
to the drive. You may have to be
repeat this. If the fault persists,
contact your local ABB representative.
2281
Calibration
Measured offset of output
phase current measurement
or difference between
output phase U2 and W2
current measurement is too
great (the values are
updated during current
calibration).
Try performing the current calibration
again.
If the fault persists, contact your local
ABB representative.
2310
Overcurrent
Output current has exceeded
internal fault limit.
In addition to an actual
overcurrent situation, this
fault may also be caused by
an earth fault or supply
phase loss.
Check motor load.
Check acceleration times in parameter
group
(speed control),
(torque control) or
(frequency control).
Also check parameters
and
.
Check motor and motor cable
(including phasing and delta/star
connection).
Check there are no contactors opening
and closing in motor cable.
Check that the start-up data in
parameter group
corresponds to the motor rating plate.
Check that there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable. See chapter
Electrical
installation
, section
Checking the
insulation of the assembly
in the
hardware manual of the drive.
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...