Fieldbus control through the embedded fieldbus interface (EFB)
385
The halt mode is controlled with bit 8 of the CiA 402 control word. When the halt
bit is set during the OPERATION ENABLED state, the drive stops and the state
machine remains in the OPERATION ENABLED state. When the bit is reset, the
drive starts running again. In all modes supporting the halt function, CiA 402
Status Word bit 10 (target reached) is set when the drive is stopped.
Note
: The drive may not necessarily stop completely as it is still the in running
(OPERATION ENABLED) state.
The following table summarizes the drive features used to perform the ramp
stop during the halt function, as well as the different halt option codes
supported by each CiA 402 operating mode. The halt option code is selected by
CANopen object 605Dh.
Status Word for the CiA 402 profile
Status word of the CiA 402 profile can be read from the object 6041h.The table
below shows the fieldbus Status Word for the CiA 402 control profile. The
embedded fieldbus interface converts the drive Status Word into this form for
the fieldbus.
Fault
Fault reaction specified by the drive. Typically a Coast stop.
Mode
Description
Halt option codes
Profile velocity Dynamic limiter ramp
1
Profile torque
Sets the torque reference to 0. Ramp depends on the
drive parameters
1
Velocity
Halt mode1: Ramp input is set to 0.
Halt mode 2,3,4: Ramp output is set to 0.
1, 2, 3, 4
Other modes
Halt bit has no effect.
N/A
Bit
Name
0
Ready to switch on
1
Switched on
2
Operation enabled
3
Fault
4
Voltage enabled
5
Quick stop
6
Switch on disabled
7
Warning
8
Drive-specific bit
9
Remote
10
Target reached
11
Internal limit active
12...13
Operation mode specific
14...15
Drive specific
Command/Event
Drive stop mode
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...