Fieldbus control through the embedded fieldbus interface (EFB)
CANopen embedded fieldbus interface operation
Control word and Status word
The Control Word (CW) is a 16-bit or 32-bit packed boolean word. It is the
principal means of controlling the drive from a fieldbus system. The CW is sent
by the fieldbus controller to the drive. With drive parameters, the user selects
the EFB CW as the source of drive control commands (such as start/stop,
emergency stop, selection between external control locations 1/2, or fault
reset). The drive switches between its states according to the bit-coded
instructions of the CW. The fieldbus CW is either written to the drive as it is or
the data is converted. See section
.
The fieldbus Status Word (SW) is a 16-bit or 32-bit packed boolean word. It
contains status information from the drive to the fieldbus controller. The drive
SW is either written to the fieldbus SW as it is or the data is converted. See
section
on page
.
References
EFB references 1 and 2 are 16-bit or 32-bit signed integers. The contents of each
reference word can be used as the source of virtually any signal, such as the
speed, frequency, torque or process reference. In embedded fieldbus
communication, references 1 and 2 are displayed by
and
respectively. Whether the references are scaled or not
Cyclic
communication
(PDO)
Acyclic
communication
SDO
CANopen objects
2001h
...
2106h
DRIVE
Select
2)
CiA 402
Data conversion
ABB Drives
Data conversion
Transparent 16
Optional reference,
actual value scaling
Transparent 32
CANopen objects
6040h
6042
6041
6044
2000h03
2000h06
6071h
6077h
60FF
606Ch
CANopen objects
4001h
...
4063h
Select
2)
1)
1)
Control word, reference, Status word and actual values
according to CANopen profile CiA 402 or ABB Drives
profile
Drive parameters
1)
Native profile
2)
Selection with CANopen EFB configuration parame-
ters (
)
Control word, reference, Status word and actual values according to Transparent 16,
Transparent 32 or ABB Drives profile
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...