
362
Fieldbus control through the embedded fieldbus interface (EFB)
Status Word
Status Word for the ABB Drives profile
The table below shows the fieldbus Status Word for the ABB Drives control
profile. The embedded fieldbus interface converts the drive Status Word into
this form for the fieldbus. The upper case boldface text refers to the states
shown in
State transition diagram for the ABB Drives profile
on page
16
FB_LOCAL_CTL
1
Local mode for control from the fieldbus is requested.
Steal control from the active source.
0
(no op)
17
FB_LOCAL_REF
1
Local mode for reference from the fieldbus is
requested. Steal reference from the active source.
0
(no op)
18
Reserved for
RUN_DISABLE_1
Not yet implemented.
19
Reserved
20
Reserved
21
Reserved
22
USER_0
Writable control bits that can be combined with drive
logic for application-specific functionality.
23
USER_1
24
USER_2
25
USER_3
26
…31
Reserved
Bit
Name
Value
STATE/Description
0
RDY_ON
1
READY TO SWITCH ON.
0
NOT READY TO SWITCH ON.
1
RDY_RUN
1
READY TO OPERATE.
0
OFF1 ACTIVE.
2
RDY_REF
1
OPERATION ENABLED.
0
OPERATION INHIBITED. See also parameter
).
3
TRIPPED
1
FAULT.
0
No fault.
4
OFF_2_STATUS
1
OFF2 inactive.
0
OFF2 ACTIVE.
5
OFF_3_STATUS
1
OFF3 inactive.
0
OFF3 ACTIVE.
Bit
Name
Value
State/Description
Summary of Contents for ACS280
Page 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Page 4: ......
Page 10: ...10 ...
Page 16: ...16 Control panel ...
Page 20: ...20 Start up ID run and use ...
Page 24: ...24 Default control connection ...
Page 88: ...88 Program features ...
Page 298: ...298 Parameters ...