i-on Range
Installer Menu Options
Page 93
operation. Once you have carried out this operation you can then scroll
through the partition list and change the allocation of the loudspeakers as
necessary.
Entry Alarm Delay
Use this option to determine what the system will do if a user strays from an
Entry Route zone during entry. (This option is available to provide compliance
with EN 50131-1.)
Select ―Disabled‖ to make the system give an alarm immediately if the user
strays from an entry route zone during entry.
Note: This is not compliant with
EN50131.
If you select ―Enabled‖ and the user strays from an entry route zone during
entry then the system waits 30 seconds before raising a full alarm. The system
also gives an internal alarm during the 30 second wait.
If the user enters an access code or presents a tag before the end of the 30
seconds internal alarm then the user can reset the system.
Abort Time
Use this option to change Alarm Abort Delay period. The timer can take any
value in the range 0 to 120 seconds.
The control unit starts the Alarm Abort Delay timer whenever it starts an
alarm. If a user silences the alarm within the Abort Delay period, the alarm will
not require an engineer or remote reset.
If an alarm occurs and a user unsets the system
within
the Alarm Abort Delay
period then the control unit activates any output of type Alarm Abort (page 62)
and starts any Alarm Abort Fast Format communications programmed.
Supervision
If a wirefree detector loses contact for more than 20 minutes then the control
unit logs the event as ―RF Warning‖. In addition, the control unit inhibits
setting. If a user overrides the inhibition then the control unit logs the event as
an RF warning override.
If a wirefree detector loses contact for more than two hours then the control
unit raises an alarm. The options available for this alarm are:
Option:
With system SET, the
control unit:
With system UNSET the
control unit:
Off
Does nothing.
Does nothing.
Fault
Logs the event (but does NOT
display any alert or fault
tone).
Displays an Alert and sounds a
fault tone and logs the event.
Tamper
Starts a Tamper alarm and
notifies the ARC with a
―Supervision‖ message.
Starts a Tamper alarm and
notifies the ARC with a
―Supervision‖ message.
Note that the Tamper option is required in Grade 2 systems in order to comply
with EN50131-1:2006+A1:2009.