Installer Menu Options
i-on Range
Page 62
Type:
(nn=shortcut)
Active when:
Assign to
Partitions?
Burglar Alarm
(03)
Any of the following zones are triggered:
Yes
Normal Alarm
Tamper (in a set system)
Entry Route
Tamper Zone (in a set system)
Entry time expires
24 hour (in a set system)
Open/Close (04) The output is active when the system (or
partition) is unset. Inactive when the
system (or partition) is set.
If you allocate this output to multiple
partitions then the output will deactivate if
any one partition is set or part set.
Note: This output is inverted relative to
other outputs, it is normally at 0V for
an unset (open) system.
Yes
Alarm Abort
(05)
An alarm in the selected partition has been
aborted by the user within the abort
period. Deactivates when the alarm is
reset.
Yes
Technical Alarm
(06)
There is a technical alarm. Deactivates
when the zone causing the alarm is
restored AND a user enters a valid access
code to acknowledge the technical alarm
alert.
Yes
Confirmed Alarm
(07)
There is a confirmed alarm. Deactivates
when the system is reset. The operation of
this output type depends on the option
selected in
System Options - Confirmation –
Confirmation Mode
(see page 84):
Basic
–
The output operates when a
second zone is activated while the
partition(s) is still in alarm.
DD243 or BS8243
–
The output activates
when a second alarm zone is triggered
within the period of the confirmation timer,
and in the same partition as the first alarm
zone to be triggered.
If the unconfirmed alarm is caused by the
expiry of the entry timer, a further two
zones which are not on the entry route
must be triggered to activate the output.
Yes