i-on Range
Appendix II
Page 195
Factory and Loading Bay. Partition 3 can be used for the Office and Reception.
To make the common area (P1) follow the status of other partitions use the
Partitions - Full Set Link option (see below).
To avoid false alarms make the alarm response of the common area (Partition
1) Siren + Comms and the other two Partitions Siren only.
Zone Programming
Location
Zone
Name
Zone Type
Partitions
Front Door
001
Front Door
Final Exit
P1
Foyer PIR
002
Foyer PIR
Entry Route
P1
Loading Bay Entrance 003
LB to Foyer
Final Exit
P2
Roller shutter
004
Rshutter
Normal Alarm
P2
Loading Bay PIR
005
LBay PIR
Entry Route
P2
Factory PIR
006
Factory PIR
Normal Alarm
P2
Factory Fire Door
007
Factory FD
24 Hour
P2
Kitchen PIR
008
Kitchen PIR
Normal Alarm
P1
Office Fire Door
009
Office FD
24 Hour
P3
Office PIR
010
Office PIR
Normal Alarm
P3
Reception PIR
011
Recpt PIR
Entry Route
P3
Reception Entrance
012
Rcept Door
Final Exit
P3
Partition and Other Programming
Menu
Sub Menu
Option
Add/delete
Detectors/Devices
External Radio Siren (if to be fitted)
Wired keypads
Keypad 01
Name = Office
Partition 3
Keypad 2
Name = Factory
Partition 2
Keypads 3 & 4
–
not
fitted
NA
Outputs
Panel Outputs
1 = Siren
2 = Strobe
3 & 4 = NU
Partitions
P1
Name = Foyer
Exit Mode = Final Door Set
Settle Time = 10s
Entry Time = 45s
Alarm Response = Siren + Comms (Full)
Strobe on Set = Yes (If required)
Strobe on Unset = Yes (if required)
P2
Name = Offices
Exit Mode = Timed
Exit Time = 20s
Entry Time = 45s
Alarm Response = Siren (Local)
P3
Name = Factory
Exit Mode = Timed
Exit Time = 20s
Entry Time = 45s