BE1-CDS220 Quick
Start
2-7
enabled and interconnected but are disabled with settings of zero. See Section 8, Application, for
diagrams that describe the BASIC-87 logic scheme.
Enter A= to gain setting access and then send each of these text files to the relay as described above
under Batch Command Text File Operations. Do not forget to add E;Y (Exit; Save Settings? Yes) to the
end of both files.
As you gain knowledge of the relay, you can experiment with the rest of the settings. To set up a file with
all user settings, enter S and the relay will respond with all settings in command format. The acceptance
test procedure in Section 13, Testing and Maintenance, provides a basic procedure for creating a file with
all user settings.
Checking the State of Inputs
Section 8, Application, shows the BASIC-87 logic diagram. Review this logic to help understand the
following discussion. In this scheme, IN1 and IN2 are being used to show the position of the breakers in
the sequence of events record (SER). Input 3 is showing the status of the 86 lockout relay. Inputs 6 to 8
can be used for alarm annunciation. You can quickly review the state of the inputs in three different ways:
one, through the front panel HMI, two, using the ASCII command interface, or three using BESTCOMS,
Metering screen.
The front panel HMI displays the input status on Screen 1.4.1, \STAT\OPER\INPUT. A diagram showing
all of the menu tree branches is located in Section 10, Human-Machine Interface. To get to this screen,
press the Up scrolling pushbutton until you reach the top screen in the current branch. You know when
you have reached the top screen because the screen stops changing when you press the Up scrolling
pushbutton. From this position, press the Right scrolling pushbutton until you have reached the screen
titled, \STATUS BE1-CDS220 REPORT STATUS. From this position, press the Down scrolling
pushbutton one time (\STAT\TARGETS) and press the Right scrolling pushbutton three times. At this
time, you should see the OPERATIONAL STATUS Screen, \STAT\OPER_STAT. If you press the Down
scrolling pushbutton from this screen, you should see the INPUTS Screen, \STAT\OPER\INPUT.
Another method would be to use the ASCII command interface. One command that you can use to see
the status of the inputs is RG-STAT. Another command is RG-INPUT. This command will only read the
status of the inputs and nothing else.
Testing
To determine if the relay is responding correctly to each test, the following commands are useful.
•
RG-TARG, (report general targets): reports the targets from the last fault.
•
RF, (report faults): reports a directory listing of the twelve fault summary reports. The fault
summary reports are numbered from 1 to 255, then wrap around, and start over. RF-### reports
the ### report.
•
RS-##, (report sequence of events record), ## events: reports the most recent ## changes of
state in the protection and control logic.
FAQ/TROUBLE SHOOTING
Frequently Asked Questions (FAQs)
1.)
Why won't the trip LED reset after pressing the Reset key on the front panel?
The Reset key is context sensitive. To reset the trip LED or the targets, the Targets screen
must be displayed. To reset the alarms, the Alarms screen must be displayed.
2.)
Is the power supply polarity sensitive?
No, the power supply will accept either an ac or dc voltage input. However, the contact sensing
for the programmable inputs is polarity sensitive. See Section 12, Installation, for a typical inter-
connection diagram.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......