13-52
Testing And Maintenance
BE1-CDS220
Table 13-42. Instantaneous 50T Element Accuracy
Sensing Type
Pickup Accuracy - Phase and Neutral
A or B (1 ampere nominal systems)
±
2% of setting or
±
10 milliamperes
D, E, or F (5 ampere nominal systems)
±
2% of setting or
±
50 milliamperes
Step 5.
After pickup occurs, slowly ramp the current down until both OUT1, OUT2, and OUT3 open.
Verify that dropout occurred as specified (95%
±
2%).
Step 6.
Repeat Steps 3, 4, and 5 for all values in Table 13-42. Optionally, reconnect the current source
to B-phase (B3, B4) and C-phase (B5, B6) inputs to test the response of all phases for each
succeeding test.
Step 7.
(Optional) Repeat steps 3 through 6 for phases B and C of the relay unless each phase was
tested in step 4. If so, skip this step and proceed to Step 8.
Step 8.
(Optional) Repeat steps 1 through 7 for the 150T and 250T elements. Use Table 13-43 or 13-
44 as a reference for substituting the commands used in Step 1.
Table 13-43. Instantaneous Overcurrent 150T Element Test Logic
Replace These Commands
With These Commands For 150T Element Tests
SL-50T=1,0 SL-150T=1,0
SL-VO1=50TPT SL-VO1=150TPT
SL-VO2=50TNT SL-VO2=150TNT
SL-VO3=50TQT SL-VO3=150TQT
SG-TARG=50T
SG-TARG=150T
SG-TRIGGER=50TPT+50TNT+50TQT,
50TQPU,0
SG-TRIGGER=150TQT,
150TQTPU,0
Table 13-44. Instantaneous Overcurrent 250T Element Test Logic
Replace These Commands
With These Commands For 250T Element Tests
SL-50T=1,0 SL-250T=1,0
SL-VO1=50TPT SL-VO1=250TPT
SL-VO2=50TNT SL-VO2=250TNT
SL-VO3=50TQT SL-VO3=250TQT
SG-TARG=50T
SG-TARG=250T
SG-TRIGGER=50TPT+50TNT+50TQT,
50TQPU,0
SG-TRIGGER=250TQT,
250TQTPU,0
Step 9.
(Optional) Repeat steps 1 through 8 for the 50T, 150T, and 250T elements in setting groups 1,
2, and 3. Use the following information as a guide to program the 50T/150T/250T elements in
higher order setting groups.
In order to program the pickup of the elements in a higher order setting group, you would
replace the
0
in the S
0
-50TP, S
0
-50TN, and S
0
-50TQ commands in Table 13-41 with a 1, 2, or
3 for setting groups 1, 2, or 3. Or, if your relay is supplied with the HMI option, you can
program each set of values by navigating to the appropriate setting group screen
\PROT\SGn\50T\50T, where n is equal to the setting group you desire. Refer to the CS/CO-
GROUP command in Section 4,
Protection and Control Functions
for more information on
changing the active setting group.
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......