6-32
Reporting and Alarm Functions
BE1-CDS220
A logic input can be used to reset the target. Using BESTCOMS, select Reporting and Alarms from the
Screens pull-down menu. Then select Fault Recording tab. The logic input can be connected by selecting
the Logic button in the Target Reset pane. When the logic input becomes TRUE, the target is reset.
BESTCOMS can also be used to review targets and alarms after an operation by selecting Metering from
the Reports pull-down menu. This screen (Figure 6-19) will contain target and alarm information.
Figure 6-19. BESTCOMS Metering Screen
Table 6-17 provides the possible targets that may be displayed on the Metering screen.
Table 6-17. Targets as Displayed
IEEE Device Number
Definition
50/150/250 ABC, N, Q
Instantaneous Overcurrents
51/151/251 ABC, N, Q
Time Overcurrents
BF Breaker
Failure
62/162 Logic
Timers
87R ABC
Phase Differential Restrained
87U Phase
Differential
Unrestrained
87ND
Neutral Differential Restrained
The RG-TARG (report general, targets) command can be used to read and reset the targets. Write
access to Reports must be gained to reset the targets using the ASCII command interface.
RG-TARG Command
Purpose:
Report/Reset Target status
Syntax:
RG-TARG
RG-TARG Command Example:
Example 1.
Read the targets from the ASCII command interface when the instantaneous overcurrent
elements (50 and 150), phase A and Neutral logged targets.
>RG-TARG
50AN; 150AN
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......