BE1-CDS220
Reporting and Alarm Functions
6-17
Figure 6-7. Reporting and Alarms Screen, Transformer Monitoring Tab
Table 6-8. Transformer Duty Monitoring Settings
Setting Range/Purpose Default
0 = Disabled
1 = Transformer monitoring enabled with duty calculated as
∑
I*t
2 = Transformer monitoring enabled with duty calculated as
∑
I
2
*t
Mode
t
= Fault clearing time
0
DMAX
Range = 0 to 4.2e+7; Increment = 1; Measured in primary amperes
0.000e+00
Circuit #
1 = Ckt # 1, 2 = Ckt # 2
1
Block
Logic
Logic expression that blocks transformer duty accumulation when TRUE.
(This parameter cannot be set through the HMI.)
0
ST-DUTY Command
Purpose:
Read/Set Transformer Duty where mode = 0/1/2 (disable/I*t/I^2*t)
Syntax:
ST-DUTY[={mode},{dmax},{ct ckt#},{BLKTXFMR logic}]
Comments:
Password Access Privilege G or Privilege S required to change settings. CT# = 1 or 2.
ST-DUTY Command Examples:
Example 1.
Enable transformer monitoring on CT 2 with duty calculated as
∑
I*t
, DMAX = 300
operations @ 20 kA with a 100 ms fault clearing time. Block accumulation of duty when
IN5 is energized.
>ST-DUTY = 1, 600E3, 2, 1N5
Example 2.
Read ST-DUTY
>ST-DUTY
2,6.000e+04,2,0
Содержание BE1-CDS220
Страница 2: ......
Страница 10: ...viii Introduction BE1 CDS220 This page intentionally left blank...
Страница 36: ...ii Quick Start BE1 CDS220 This page intentionally left blank...
Страница 48: ...ii Input And Output Functions BE1 CDS220 This page intentionally left blank...
Страница 66: ...iv Protection and Control BE1 CDS220 This page intentionally left blank...
Страница 112: ...ii Metering BE1 CDS220 This page intentionally left blank...
Страница 116: ...5 4 Metering BE1 CDS220 This page intentionally left blank...
Страница 166: ...ii BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 176: ...7 10 BESTlogic Programmable Logic BE1 CDS220 This page intentionally left blank...
Страница 234: ...8 56 Application BE1 CDS220 This page intentionally left blank...
Страница 236: ...ii Security BE1 CDS220 This page intentionally left blank...
Страница 240: ...9 4 Security BE1 CDS220 This page intentionally left blank...
Страница 242: ...ii Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 256: ...10 14 Human Machine Interface BE1 CDS220 This page intentionally left blank...
Страница 258: ...ii ASCII Command Interface BE1 CDS220 This page intentionally left blank...
Страница 289: ...BE1 CDS220 Installation 12 7 Figure 12 8 MX Case Horizontal Panel Mount Front View Overall Dimensions...
Страница 422: ...14 32 BESTCOMS Software BE1 CDS220 This page intentionally left blank...
Страница 424: ...ii Time Current Characteristics BE1 CDS220 This page intentionally left blank...
Страница 441: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 17 Figure A 13 Time Characteristic Curve A Standard Inverse 99 1621...
Страница 442: ...A 18 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376...
Страница 443: ...BE1 CDS220 Time Overcurrent Characteristic Curves A 19 Figure A 15 Time Characteristic Curve C Extremely Inverse 99 1377...
Страница 444: ...A 20 Time Overcurrent Characteristic Curves BE1 CDS220 Figure A 16 Time Characteristic Curve G Long Time Inverse 99 1622...
Страница 452: ...ii Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 456: ...C 4 Terminal Communication BE1 CDS220 This page intentionally left blank...
Страница 458: ...ii Settings Calculations BE1 CDS220 This page intentionally left blank...
Страница 475: ......